Product Usage :
This product is suitable for power frequency distribution voltage 3.6 /6kV ~ 26 / 35kV transmission and distribution lines.
Implementation standards :
Implementation of GB / T12706.2 andGB / T12706.3 standards.
For flame-retardant, low-halogenlow-smoke flame-retardant, halogen-free low smoke flame retardant series ofpower cables, but also the implementation of GB / T19666, the flame retardantproperties in line with GB / T 18380 requirements;
For anti-termite cable power cableits anti-termite properties in line with JB / T 10696.9 requirements.
Type :
Note:For flame-retardant power cable, “Z(ZA- 、ZB- 、ZC-)” is added before the above type number ;anti-termite power cable, "FY-" is added before the abovetype number;intelligent on-line temperature monitoring cable, "DFTS-"is added before the above type number.
1 、single-corearmored cable for the exchange system, should be non-magnetic material armored.
Product specifications :
Use features :
1 、rated temperature
Long-term maximum allowable operatingconductor temperature: 90 °C,Maximum operating temperature under short-timeoverload: 130°C,Maximum operating temperature under short circuit (shortcircuit duration 5 s): 250 °C
2 、required
2.1 Cablelaying shall not be restricted by drop height; theambient temperature for laying shall not be lower than 0 °C, and if the ambienttemperature is lower than 0 °C, the cable shall be pre-heated
2.2 Minimum allowable bending radius for cable installation